                        35KV及以下銅、鋁芯電力電纜

                        聚氯乙烯絕緣電力電纜
                        日期:08-20

                          產(chǎn)品標(biāo)準(zhǔn)

                          Standard

                          本產(chǎn)品按GB12706《額定電壓35KV及以下銅芯、鋁芯塑料絕緣電力電纜》標(biāo)準(zhǔn)生產(chǎn),同時還可根據(jù)用戶需要按國際電工委員會推薦標(biāo)準(zhǔn)IEC、英國標(biāo)準(zhǔn)、德國標(biāo)準(zhǔn)及美國標(biāo)準(zhǔn)生產(chǎn)。

                          The product is manufactured according to the standard of GB12706 or IEC , BS , DIN and ICEA upon request

                          適合范圍

                          Applications

                          本產(chǎn)品適用于額定電壓35KV及以下配電網(wǎng)或工業(yè)裝置中固定敷設(shè)之用。

                          The product is suitable for use in power distribution networks or fixed installations for industrial equipments with rated voltage up to and including 35KV.

                          使用特性

                          Operating characteristics

                          1、 ● 額定電壓3.6/6KV~26/35KV交聯(lián)聚乙烯絕緣電力電纜

                          XLPE Insulated Electrical Cable for rated power frequency voltage Uo/U:3.6/6KV~26/35KV.

                          ● 電纜導(dǎo)體的允許長期高工作溫度為90℃。

                          Max.permissible continuous operating temperature of conductor:90℃

                          ● 短路時(長持續(xù)時間不超過5s)電纜導(dǎo)體的高溫度不超過250℃。

                          Max.short-circuit temperature of conductor shall not exceed 250℃.(5s Max. Duration)

                          ● 敷設(shè)電纜時環(huán)境溫度應(yīng)不低于0℃。

                          The bending radius of single-core cable shall not less than 20 times of the cable diameter

                          The bending radius of three-cores cable shall not less than 15 times of the cable diameter

                          2、 ● 額定電壓0.6/1kv交聯(lián)聚乙烯絕緣電力電纜

                          XLPE Insulated Electrical Cable for rated power frequency voltage Uo/U : 0.6/1KV

                          ● 電纜導(dǎo)體的允許長期高工作溫度為90℃。

                          Max.permissible continuous operating temperature of conductor : 90℃

                          ● 短路時(長持續(xù)時間不超過5s)電纜導(dǎo)體的高溫度不超過250 ℃

                          Max.short-circuit temperature of the conductor shall not exceed 250 ℃

                          ● 敷設(shè)電纜時環(huán)境溫度應(yīng)不低于0 ℃

                          The ambient temperature under installation shall not below 0 ℃

                          ● 電纜彎曲半徑不小于電纜外徑15倍

                          The bending radius of a cable shall not less than 15 times of the cable diameter .

                          3、 ● 額定電壓0.6/1KV聚氯乙烯絕緣電力電纜。

                          PVC Insulated Electrical Cable for rated power frequency voltage Uo/U : 0.6/1KV

                          ● 電纜導(dǎo)體的允許長期高工作溫度為70 ℃

                          Max.permissible continuous operating temperature of conductor : 70 ℃

                          ● 短路時(長持續(xù)時間不超過5s)電纜導(dǎo)體高溫度不超過:160℃

                          Max.short-circuit temperature of the conductor shall not exceed :160℃

                          ● 敷設(shè)電纜時環(huán)境溫度應(yīng)不低于0 ℃

                          The ambient temperature under installation shall not below 0 ℃

                          ● 電纜彎曲半徑不小于電纜外徑10倍

                          The bending radius of a cable shall not be less than 10 times of the cable diameter.

                          電纜額定電壓的選擇

                          Voltage designation

                          ● 電纜的額定電壓應(yīng)適合于電纜使用系統(tǒng)的運行狀況,用Uo/U(Um)kv表示。

                          Uo—電纜設(shè)計用的導(dǎo)體與屏蔽或金屬套之間的額定工頻電壓;

                          U—電纜設(shè)計用的導(dǎo)體之間的額定工頻電壓;

                          Um—設(shè)備可承受的“高系統(tǒng)電壓”的大值。

                          The rated voltage of the cable for a given application shall be suitable for the operating conditions in the system in which the cable is used , and is expressed in the form Uo/U(Um)kv .

                          Where:

                          Uo—The rated power-frequency voltage between conductor and screen or metallic-sheath , for which the cable designed;

                          U — The rated power –frequency voltage between conductors , for which the cable designed ;

                          Um—The maximum value of the “highest system voltage “ for which the equipment may be operated.

                          注:第一類——用于單相接地故障時間每一次一般不大于1min, 亦可用于長不超過8h , 第年累計不超過125h 的系統(tǒng)。

                          第二類一一用于接地故障時間更長的系統(tǒng)及對電纜絕緣性能要求較高的場合。

                          The first class cable-suitable for one single-phase earth-fault time does not exceed 1 min each time and Max.

                          Time not exceed 8 hours , and not exceed 125 hours in all in one year.

                          The second class cable suitable for more the earth-fault time and more better insulation performance

                        jenniferweiyi@outlook.com 售后服務(wù)
                        電話:0510-87904320
                        傳真:0510-87233666
                        客服時間:(9:00-18:00)